Section 4: Basic Configuration/Start-Up
January 2015
Basic Configuration/Start-Up
Upper null zone
This parameter should only be changed if there are measurement problems in the upper part of
the tank. Such problems may occur if there are disturbing objects close to the probe. By setting
the Upper Null Zone (UNZ), the measuring range is reduced. See Disturbances at the top of the
tank on page 102 for further information.
Note
Measurements are not performed within the UNZ.
4 mA point
The 4 mA point must be set above the lower transition zone (see Transition zones on page 16).
If the 4 mA point is set to a point within the transition zone or below the probe end, the full
range of the analog output is not used.
20 mA point
Make sure the 20 mA point is below the upper null zone.
The 20 mA point must be set below the upper transition zone (see Transition zones on
page 16). If the 20 mA point is set to a point within the transition zone, the full range of the
analog output is not used.
Probe angle
If the transmitter is not mounted vertically, the angle from the vertical position must be given.
4.2.2 Volume configuration
For volume calculations, you can select one of the standard tank shapes or the strapping option.
Select None if volume calculation is not used.
Tank type
You can select one of the following options:
Strap table
Vertical cylinder
Horizontal cylinder
Vertical bullet
Horizontal bullet
Sphere
None