52
Reference Manual
00809-0100-4811, Rev DA
Section 3: Installation
January 2015
Installation
3. Adjust distance by shifting hole for split pin in lower bushing.
4. Insert the split pins through the bushings and the probe.
5. Secure the split pins.
3.6 Electrical installation
3.6.1 Cable/conduit entries
The electronics housing has two entries for ½ - 14 NPT. Optional M20×1.5 and PG 13.5 adapters
are also available. The connections are made in accordance with local or plant electrical codes.
Make sure unused ports are properly sealed to prevent moisture or other contamination from
entering the terminal block compartment of the electronics housing.
Note
Remove any orange caps that may be attached. Use the enclosed metal plug to seal the unused
port.
3.6.2 Grounding
The housing should always be grounded in accordance with national and local electrical codes.
Failure to do so may impair the protection provided by the equipment. The most effective
grounding method is direct connection to earth ground with minimal impedance. There are
0.16 in. (4 mm)
0.08 in. (2 mm)