Section 3: Installation
January 2015
Installation
Flexible single lead
Pipe diameter Ø 4 in. (100 mm).
Note
For smaller pipes, please consult factory.
Make sure the probe is at the center of the still pipe by, for example, using a centering disc.
Figure 3-5. Rigid Single and Flexible Single Probes in Still Pipes
Note
It is not recommended that flexible probes are installed in bypass pipes.
Rigid twin lead
Pipe diameter Ø 2 in. (50 mm)
Inlet pipe diameter N < Ø
L 12 in. (300 mm)
The center rod must be placed more than 0.6 in./15 mm away from the pipe wall.
Flexible twin lead
Pipe diameter Ø 4 in. (100 mm)
Note
For smaller pipes, please consult factory.
The center rod must be placed more than 0.6 in./15 mm away from the pipe wall. The probe
may under no circumstances get into contact with the pipe wall. It is recommended that a
centering disc is used.
Ø
L
N
Rigid single
Ø
Flexible single