199
Reference Manual
00809-0100-4811, Rev DA
Appendix C: Rosemount 3300 Series with HART
®
to Modbus
®
Converter
January 2015
Rosemount 3300 Series with HART
®
to Modbus
®
Converter
C.11 Specific Modbus host configuration
The Remote Terminal Unit needs to be configured to communicate and correctly interpret data
when reading input registers from the Rosemount 3300 Series Transmitter.
Baud rate
The specified baud rates below are recommendations. If other baud rates are used, make sure
that the Rosemount 3300 Series Transmitter and the RTU are configured for the same
communication speed.
Floating Point Format Code
See “Common Modbus host configuration” on page 195.
RTU Data Type
The RTU Data Type specifies which configuration to use in the RTU in order for the RTU to
correctly interpret a floating point number transmitted from the Rosemount 3300 Series
Transmitter with Modbus.
Input Register Base Number
Data registers in the Rosemount 3300 Series Transmitter with Modbus are numbered exactly as
they are transmitted in the Modbus communication. Some RTUs use different naming
conventions and to configure the RTU to poll the correct registers from the 3300 Modbus, an
Input Register Base Number is stated for each RTU respectively. For example, if the input register
base number is 1 for the RTU, the 3300 Modbus input register 1302 has to be entered in the RTU
address as input register 1303.
C.11.1 Emerson Process Management ROC800 Series
Figure C-8. Wiring Diagram for Connecting 3300 Modbus to Emerson Process
Management ROC800 Series
RS-485
A (RX/TX+)
B (RX/TX-)
Y
Z
COM
MA (+)
MB (-)
PWR +
PWR -
ROC800 Series
3300 Modbus
Power Supply
+ 8 to + 30 Vdc
(max. rating)
GND